We are a leading of silicone rubber insulated single core cables sif red 1 x 2.5 sq mm part no. 23702, make helukabel from Ghaziabad, India.

Silicone Rubber Insulated Single Core Cables SiF red 1 x 2.5 sq mm Part no. 23702, Make Helukabel

Request Callback

₹ 69 / Meter Get Latest Price

Product Brochure
Conductor Size2.5 sqmm
Temperature Rating–40 to 180°C
Voltage Rating450 V
Conductor MaterialTinned Copper
Wire TypeSingle Core
Insulation WallStandard Wall
ColorRed
Flame RatingFRLS
ApprovalsUL, VDE, RoHS, CE

SiF red 1 x 2.5 mm²Part no. 23702

Silicone single core

finely stranded

tinned wire

increased temperature resistance

Item Details

Part no.23702

Item description: SiF red 1 x 2.5 mm²

Core Colour:red

AWG (approx.): 14

Outer Ø mm (approx.): 3.4

Cu factor per km: 24.0

Weight kg/km (approx.): 30.0

Copper base in EUR / 100 kg: 150

Metres per Packaging Unit:100

Cut-to-length service available:no

EAN / GTIN: 4060892252174

Customs tariff number: 85444995

Technical Data

Silicone single core in alignment with DIN VDE 0250-1, DIN VDE 0250-502

Temperature range

flexible -25°C to +180°C
fixed -60°C to +180°C

Permissible operating temperature of the conductor

+180°C

Nominal voltage

AC U0/U 300/500 V

Test voltage

2000 V

Breakdown voltage

5000 V

Minimum bending radius

flexible 15x Outer-Ø
fixed 6x Outer-Ø

Cable Structure

Copper wire tinned, finely stranded, 0.5 - 185 mm²: acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5

Strand construction:

0.25 mm²: approx. 8 x 0.2 mm

Core insulation: silicone

Core identification: see datasheet

Properties

resistant to: ozone, oxygen, alcohols, dilute acids, alkalis, saline solutions, oxidising agents, high molecular weight oils, vegetable and animal fats, plasticisers and clophen, seawater

halogen-free

high flash point

Tests

halogen-free acc. to DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1

corrosiveness of combustion gases acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2

flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2

certifications and approvals:

EAC

Notes

the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only

for fixed installation, always install in open, ventilated pipe or duct systems; otherwise, a combination of high temperatures above 90°C and the absence of air would affect the mechanical properties of silicone

Application

Temperature resistant silicone single core for use in iron, steel and rolling mills, foundries, cement, glass and ceramic factories as well as in aircraft construction and ship building.